Site Map

Home

Products

Success Stories

About Us

Resources

What's New

Contact Us










  Products    Technical Details
Technical Details
PLEASE NOTE: Type A and B (according to IEC 60755) refer to the following:

Type A refers to systems running on AC or pulsed DC power.
Type B refers to systems running on AC, pulsed DC, and/or pure/rectified DC power, such as systems running variable frequency drives.


Part Name
System Type
IEC60755 Type
Supply Voltage
Supply Freq.
Response Values
Number of Channels
Response 1, A type
Response 1, B type
Response 2, A type
Response 2, B type
Rated Freq., A type
Rated Freq., B type
Response Time
Resp. Delay, Prealarm
Resp. Delay, Alarm
Starting Delay
Delay on Release
Interface
Relay, Prealarm
Relay, Alarm
Displays
Power LED
Alarm LED
Display Type
Design
CTs
External / Internal
Usable CT, A type
Usable CT, B type
Connection Monitor
General Features
Buttons
Fault Memory
Memory History
Harmonics Analysis
Preset
Master / Slave
Parameter Set
Internal Clock
BMS Addr. Range
Freq. Resp.
Approvals
Datasheet
RCMS460-D
A or B
DC 16 - 94 V, 70 - 276 V; AC 16 - 72 V, 70 - 276 V
DC, AC 42 - 460 Hz
12
6 mA - 20 A
10 mA - 10 A
6 mA - 20 A
10 mA - 10 A
42 - 2000 Hz
0 - 2000 Hz
<= 180 ms, <= 30 ms
0 - 999 s
0 - 999 s
0 - 99 s
0 - 999 s
RS-485 (BMS protocol)
1 SPDT contact
1 SPDT contact
Yes
Alarm 1, 2
LCD graphics display
Digital
Exterior
W, WR, WS series
W(AB) series
Yes
INFO, TEST, RESET, MENU
Selectable
Yes
Yes
Yes
Yes
Yes
Yes
1 - 90
Yes
UL, GOST



Ordering Information


Part Name Ordering Number Setpoint Range Supply Voltage
RCMS460-D
RCMS460-D-16 mA - 20 AAC 16-72 V, DC 16-94 V
RCMS460-D-26 mA - 20 AAC 70-276 V, DC 70-276 V



700 Fox Chase - Coatesville PA 19320 USA
Phone: 610-383-9200 / Fax: 610-383-7100 - Toll Free: 1-800-356-4266
To request more information, use our online form