Part Name
|
|
System Type
|
|
IEC60755 Type
| |
Supply Voltage
|
|
Supply Freq.
|
|
Response Values
|
|
Number of Channels
|
| Response 1 | | Response 2 | | Rated Frequency |
|
Response Time
|
|
Resp. Delay, Prealarm
|
|
Resp. Delay, Alarm
|
|
Starting Delay
|
|
Delay on Release
|
|
Interface
|
|
Relay, Prealarm
|
|
Relay, Alarm
|
|
Displays
|
|
Power LED
|
|
Alarm LED
|
|
Display Type
|
|
Design
|
|
CTs
|
|
External / Internal
|
| Usable CT |
|
Connection Monitor
|
|
General Features
|
|
Buttons
|
|
Fault Memory
|
|
Memory History
|
|
Approvals
|
|
Datasheet
|
|
|
|
RCMA420
|
|
|
|
B
| |
AC 16 - 72 V; DC 9.6 - 94 V; AC/DC 70 - 300 V
|
|
40 - 400 Hz
|
|
|
|
1
|
|
50 - 100% of Alarm
|
|
10 - 500 mA
|
|
0 - 2000 Hz
|
|
<= 180 ms, <= 30 ms
|
|
0 - 10 s
|
|
0 - 10 s
|
|
0 - 10 s
|
|
0 - 99 s
|
|
No
|
|
1 SPDT contact
|
|
1 SPDT contact
|
|
|
|
Yes
|
|
Alarm 1, 2
|
|
Seven segment
|
|
Digital
|
|
|
|
Exterior
|
|
W20AB, W35AB, W60AB
|
|
Yes
|
|
|
|
TEST, RESET, MENU
|
|
Selectable
|
|
Yes
|
|
UL, GOST
|
|
|
|