Site Map

Home

Products

Success Stories

About Us

Resources

What's New

Contact Us










  Products    Technical Details
Technical Details
PLEASE NOTE: Type A and B (according to IEC 60755) refer to the following:

Type A refers to systems running on AC or pulsed DC power.
Type B refers to systems running on AC, pulsed DC, and/or pure/rectified DC power, such as systems running variable frequency drives.


Part Name
System Type
IEC60755 Type
Supply Voltage
Supply Freq.
Response Values
Number of Channels
Response 1
Response 2
Rated Frequency
Response Time
Resp. Delay, Prealarm
Resp. Delay, Alarm
Starting Delay
Delay on Release
Interface
Relay, Prealarm
Relay, Alarm
Displays
Power LED
Alarm LED
Display Type
Design
CTs
External / Internal
Usable CT
Connection Monitor
General Features
Buttons
Fault Memory
Memory History
Approvals
Datasheet
RCM460Y
A
AC 90 - 132 V, 230 V
40 - 400 Hz
1
30 - 300 mA
No
40 - 400 Hz
<= 300 ms, <= 40 ms
No
0 - 1 s
No
No
No
No
1 SPDT contact
Yes
Yes
No
Analog
Exterior
W, WR, WS series
Yes
TEST (internal)
Selectable
No
UL, GL, GOST



Ordering Information


Part Name Ordering Number Setpoint Range Supply Voltage
RCM460Y
RCM460Y30 mA - 300 mAAC 230 V
RCM460Y-1330 mA - 300 mAAC 90-132 V
RCM460Y-711310 mA - 100 mAAC 120 V
RCM460Y-7110 mA - 100 mAAC 230 V



700 Fox Chase - Coatesville PA 19320 USA
Phone: 610-383-9200 / Fax: 610-383-7100 - Toll Free: 1-800-356-4266
To request more information, use our online form
or email us at: info@bender.org