Part Name
|
|
General Info
|
|
Application
|
|
Digital or Analog
|
|
Technical Data
|
|
Voltage
|
|
Coupler Compatible
|
|
Frequency
|
|
System Leakage Capac.
|
|
Response
|
|
Range
|
|
Response Values
|
|
Contacts
|
|
Alarm
|
|
Prewarning
|
|
System Fault
|
|
Interface
|
|
RS-485
|
|
Test/Reset Buttons
|
|
Other Features
|
|
Measuring Principle
|
|
Fault Memory
|
|
Fault Selector
|
|
Connection Monitoring
|
|
EDS Locator Connectivity
|
|
Datasheet
|
|
|
|
IR470LY2
|
|
|
|
Main Circuits: AC, 3(N)AC
|
|
Analog
|
|
|
|
0 - 793 V
|
|
Yes
|
|
40 - 460 Hz
|
|
20 μF
|
|
|
|
10kΩ - 100kΩ / 35kΩ - 500kΩ
|
|
2
|
|
|
|
1 SPDT contact
|
|
1 SPDT contact
|
|
No
|
|
|
|
No
|
|
Internal/External
|
|
|
|
DC
|
|
Yes
|
|
No
|
|
Yes
|
|
No
|
|
|
|
|
IR470LY2
|
|
|
|
Main Circuits and De-Energized Loads
|
|
Analog
|
|
|
|
0 - 793 V
|
|
Yes
|
|
40 - 460 Hz
|
|
10 μF
|
|
|
|
100kΩ - 1MΩ / 500kΩ - 5MΩ
|
|
2
|
|
|
|
1 SPDT contact
|
|
1 SPDT contact
|
|
No
|
|
|
|
No
|
|
Internal/External
|
|
|
|
DC
|
|
Yes
|
|
No
|
|
Yes
|
|
No
|
|
|
|
|
|